Contactor de CA LC1-D1210 12A 220V
Tipo de designación
Parámetro técnico
midel | 2 Sección transversal de cableado (cu) | Tamaño del tornillo | Par de apriete (N. m) | |||
numero de pieza | Cable flexible con casquillo soldado en frío (mm2) | Cable flexible sin casquillo prensado en frío (mm2) | Cable inflexible (mm2) | |||
JLC1-09 | 1-2 | 2.5 | 4 | 4 | M3.5 | 0,8 |
JLC1-12 | 1-2 | 2.5 | 4 | 4 | M3.5 | 0,8 |
JLC1-18 | 1-2 | 4 | 6 | 6 | M3.5 | 0,8 |
JLC1-25 | 1 | 4 | 10 | 6 | M4 | 1.2 |
2 | 4 | 6 | 6 | M4 | 1.2 | |
JLC1-32 | 1 | 4 | 10 | 6 | M4 | 1.2 |
2 | 4 | 6 | 6 | M4 | 1.2 | |
JLC1-40 | 1 | 10 | 16 | 10 | M4 | 3.5 |
2 | 10 | 10 | 10 | M8 | 3.5 | |
JLC1-50 | 1 | 16 | 25 | 25 | M8 | 3.5 |
2 | 16 | 16 | - | M8 | 3.5 | |
JLC1-65 | 1 | 16 | 25 | 25 | M8 | 3.5 |
2 | 16 | 16 | - | M8 | 3.5 | |
JLC1-80 | 1 | 50 | 50 | 50 | M8 | 3.5 |
2 | 25 | 35 | - | M10 | 4.0 | |
JLC1-95 | 1 | 50 | 20 | 50 | M10 | 4.0 |
2 | 25 | 35 | - | M10 | 4.0 |
Dimensiones totales y de montaje (mm)
Escenarios de aplicación:
Generalmente se instala en la caja de distribución en el piso, centro de computación, sala de telecomunicaciones, sala de control de ascensores, sala de televisión por cable, sala de control de edificios, centro de bomberos, área de control automático industrial, sala de operaciones de hospitales, sala de monitoreo y equipos de cajas de distribución con dispositivos médicos electrónicos. .
Escribe aquí tu mensaje y envíanoslo